

The PTK-12-MIL-HI generator, tailored specifically to meet the power requirements of military operations, notably within the compact confines of the S-788 Humvee-mounted shelter.

The PTK-10-TRAP generator was designed to meet the unique challenges posed by the cramped confines of military scout vehicles.

Focused on portability, quick assembly, and ease of use, this project highlights the importance of responsive solutions in emergency situations.
Generator spec sheets list output in kVA (kilovolt-amperes), but breakers, wiring, transfer switches, and load calculations all work in amps. Converting between the two is essential for sizing a generator correctly, and the formula changes depending on whether you’re running single-phase or three-phase power.
Below you’ll find the formulas, worked examples, and quick-reference charts for the most common generator voltages. If your spec sheet lists kilowatts instead, see our guide on converting kW to amps for generators.
Single-phase:
Amps = (kVA × 1,000) ÷ Voltage
Three-phase:
Amps = (kVA × 1,000) ÷ (Voltage × 1.732)
The 1.732 in the three-phase formula is the square root of 3 (√3), which accounts for power being delivered across three conductors. Use the line-to-line voltage (e.g., 208V, 480V) in the three-phase formula.

Example 1 — 50 kVA single-phase at 240V:
Amps = (50 × 1,000) ÷ 240 = 208.3 amps
Example 2 — 150 kVA three-phase at 480V:
Amps = (150 × 1,000) ÷ (480 × 1.732) = 150,000 ÷ 831.4 = 180.4 amps
Example 3 — going the other way (amps to kVA), 400A service at 208V three-phase:
kVA = (400 × 208 × 1.732) ÷ 1,000 = 144.1 kVA — so you’d look at a 150 kVA generator at minimum, and larger once headroom is factored in.

Common single-phase voltages in North America are 120V and 240V.
| Generator Size (kVA) | Amps at 120V | Amps at 240V |
|---|---|---|
| 5 | 41.7 | 20.8 |
| 10 | 83.3 | 41.7 |
| 15 | 125.0 | 62.5 |
| 20 | 166.7 | 83.3 |
| 25 | 208.3 | 104.2 |
| 30 | 250.0 | 125.0 |
| 40 | 333.3 | 166.7 |
| 50 | 416.7 | 208.3 |
| 60 | 500.0 | 250.0 |
| 75 | 625.0 | 312.5 |
| 100 | 833.3 | 416.7 |
| 125 | 1,041.7 | 520.8 |
| 150 | 1,250.0 | 625.0 |
| 200 | 1,666.7 | 833.3 |
| 250 | 2,083.3 | 1,041.7 |
| 300 | 2,500.0 | 1,250.0 |
| 400 | 3,333.3 | 1,666.7 |
| 500 | 4,166.7 | 2,083.3 |
| 625 | 5,208.3 | 2,604.2 |
| 750 | 6,250.0 | 3,125.0 |
| 1000 | 8,333.3 | 4,166.7 |

Three-phase is standard for commercial and industrial generators. Values below use line-to-line voltage and √3 = 1.732.
| Generator Size (kVA) | Amps at 208V | Amps at 240V | Amps at 480V |
|---|---|---|---|
| 5 | 13.9 | 12.0 | 6.0 |
| 10 | 27.8 | 24.1 | 12.0 |
| 15 | 41.6 | 36.1 | 18.0 |
| 20 | 55.5 | 48.1 | 24.1 |
| 25 | 69.4 | 60.1 | 30.1 |
| 30 | 83.3 | 72.2 | 36.1 |
| 40 | 111.0 | 96.2 | 48.1 |
| 50 | 138.8 | 120.3 | 60.1 |
| 60 | 166.5 | 144.3 | 72.2 |
| 75 | 208.2 | 180.4 | 90.2 |
| 100 | 277.6 | 240.6 | 120.3 |
| 125 | 347.0 | 300.7 | 150.4 |
| 150 | 416.4 | 360.8 | 180.4 |
| 200 | 555.1 | 481.1 | 240.6 |
| 250 | 693.9 | 601.4 | 300.7 |
| 300 | 832.7 | 721.7 | 360.8 |
| 400 | 1,110.3 | 962.3 | 481.1 |
| 500 | 1,387.9 | 1,202.8 | 601.4 |
| 625 | 1,734.8 | 1,503.5 | 751.8 |
| 750 | 2,081.8 | 1,804.2 | 902.1 |
| 1000 | 2,775.7 | 2,405.6 | 1,202.8 |
kVA is apparent power; kW is real power. The two are linked by the power factor (PF):
kW = kVA × Power Factor
Most diesel generators are rated at a 0.8 power factor, so a 100 kVA generator delivers about 80 kW of usable power. Resistive loads like heaters run near PF 1.0, while motors and compressors typically run at 0.8–0.9. When a spec sheet gives you kW instead of kVA, use our kW to amps conversion guide.
Getting the kVA-to-amps conversion right protects you on both ends:
Undersizing trips breakers, stalls motor starts, and can damage both the generator and connected equipment. Oversizing wastes capital and causes wet stacking in diesel engines that run at light load for long periods.
A good rule of thumb is to calculate your total running amps, account for motor starting inrush (often 2–3× running current), then add 20–25% headroom. If you’d like help selecting the right unit, contact our team — we size generators for residential, commercial, and industrial applications every day.
A 100 kVA three-phase generator delivers about 277.6 amps at 208V, 240.6 amps at 240V, or 120.3 amps at 480V. On single-phase 240V it would deliver about 416.7 amps.
For single-phase: Amps = (kVA × 1,000) ÷ Voltage. For three-phase: Amps = (kVA × 1,000) ÷ (Voltage × 1.732), where 1.732 is the square root of 3.
No. kVA is apparent power and kW is real power. They are related by the power factor: kW = kVA × power factor. Most generators are rated at a 0.8 power factor, so a 100 kVA generator provides about 80 kW.
kVA describes the total electrical output regardless of the load’s power factor. Since the generator manufacturer can’t know what power factor your equipment will run at, kVA is the universal rating; kW depends on your specific load.
kVA = (Amps × Volts × 1.732) ÷ 1,000 = (200 × 480 × 1.732) ÷ 1,000 ≈ 166 kVA. Add 20–25% headroom and you’d typically select a 200 kVA unit.